Brief description:Performance and Features: ◆ Nominal diameter: DN15... DN500; ◆ Ideal flow regulation characteristics, with relative flow rate and relative opening showing a linear relationship; ◆ Precise valve opening indication, accurate to 1% of the valve's full opening; ◆ Reliable opening lock memory function; ◆ Excellent cutoff function; ◆ EPDM sealing ensures reliable sealing performance; ◆ Valve body, stem, and valve core can be supplied with gray iron according to different user requirements
Update time
View count
PRODUCT CLASSIFICATION
Performance and Features:
◆ nominal diameter: DN15... DN500;
Ideal flow regulation characteristics, with a linear relationship between relative flow and relative opening;
Accurate valve opening indication, able to be precise to 1% of the valve's full opening degree;
◆ Reliable opening locking memory function;
Excellent cut-off function;
EPDM sealing, reliable sealing performance;
The valve body, valve stem, and valve core can be provided with gray iron GJL250, ductile iron GGG450-10, stainless steel or brass materials according to different user requirements;
Threaded and flanged connections, with connection standards compliant with EN10226 and EN1092-1/2;
◆ Compliant with PED and valve special equipment manufacturing license.
Purpose:
1. Building air conditioning or heating pipeline network
To meet energy-saving requirements, it is necessary to ensure that all main and branch pipes of the air conditioning and heating pipeline system in buildings meet the design flow rate. At this point, balance valves should be installed on the main, main, riser, and branch pipes.
2. Residential heating pipeline network
The heating network in residential areas is often supplied by boiler rooms or thermal stations to several buildings. Due to the different distances between each building and the heat source, if there is no effective equipment to eliminate the residual pressure head near the loop, the flow distribution will not meet the design requirements, resulting in overheating at the near end and undercooling at the far end. Balance valves should be installed on each main and branch pipe to ensure flow balance between each main pipe and each building.
3. Heat exchanger group cargo chiller unit
When heat exchange units or chiller units are installed in parallel, if the flow rate of each unit is not consistent with its rated flow rate, it will prevent the units from operating efficiently. In this case, a balance valve should be installed at each heat exchange unit or chiller unit to ensure that each unit can reach the design flow rate and operate safely and normally.
4. Thermal power station
In a system that supplies hot water or steam to several thermal power stations in a thermal power station or boiler room, a balance valve should be installed on the primary loop side of each thermal power station to ensure that each station receives the required flow rate. To ensure that the flow rate of each secondary loop is the design flow rate, balance valves should also be installed on each secondary loop side of the thermal station.
Model Description:
Example: MBCV015-0SP02
1. Abbreviation for "MBCV" Static Balancing Valve;
2. "015" caliber DN15;
3. "-" delimiter;
4. "0S" standard configuration, threaded connection;
0F "standard configuration, flange connection;
5. "P02" pressure rating, abbreviated as PN25, "P01": PN16
Special requirements can be noted at the end.
Parameter table: MBCV: DN15-50 brass
Model/PN16 | Model/PN25 | pipe diameter(in.) | DN(mm) | Kvs(m³/h) | Temperature(℃) |
MBCV015-0SP01 | MBCV015-0SP02 | 1/2" | 15 | 3.88 | -10~120℃ |
MBCV020-0SP01 | MBCV020-0SP02 | 3/4" | 20 | 5.72 | |
MBCV025-0SP01 | MBCV025-0SP02 | 1" | 25 | 8.90 | |
MBCV032-0SP01 | MBCV032-0SP02 | 1-1/4" | 32 | 19.5 | |
MBCV040-0SP01 | MBCV040-0SP02 | 1-1/2" | 40 | 27.50 | |
MBCV050-0SP01 | MBCV050-0SP02 | 2" | 50 | 38.5 |
Note: 1. Flow deviation ≤ 5%;
2. The valve body and valve core are available in two materials: brass and bronze.
Parameter table: MBCV: DN50-500 cast iron
Model/PN16 | Model/PN25 | pipe diameter(in.) | DN(mm) | Kvs(m³/h) | Temperature(℃) |
MBCV050-0FP01 | MBCV050-0FP02 | 2 | 50 | 55.6 | -10~120℃ |
MBCV065-0FP01 | MBCV065-0FP02 | 2.5" | 65 | 92.74 | |
MBCV080-0FP01 | MBCV065-0FP02 | 3" | 80 | 114.5 | |
MBCV100-0FP01 | MBCV100-0FP02 | 4" | 100 | 187.5 | |
MBCV125-0FP01 | MBCV125-0FP02 | 5" | 125 | 286.5 | |
MBCV150-0FP01 | MBCV150-0FP02 | 6" | 150 | 395 | |
MBCV200-0FP01 | MBCV200-0FP02 | 8" | 200 | 758 | |
MBCV250-0FP01 | MBCV250-0FP02 | 10" | 250 | 1102.5 | |
MBCV300-0FP01 | MBCV300-0FP02 | 12" | 300 | 1516.6 | |
MBCV350-0FP01 | MBCV350-0FP02 | 14" | 350 | 2420 | |
MBCV400-0FP01 | MBCV400-0FP02 | 16" | 400 | 3050 | |
MBCV450-0FP01 | MBCV450-0FP02 | 18" | 450 | 3720 | |
MBCV500-0FP01 | MBCV500-0FP02 | 20" | 500 | 4180 |
Precontent Dynamic balancing electric control valve